Purge Air to Water Exchanger

ClassificationGas cooler, Shell & Tube, removable u-bundle, removable bonnet header.
FeaturesTurbine application where purge air must be cooled. Compact cooler for integration into the customer system with low pressure drop.

Purge Air to Water Exchanger

The air is cooled by using cooling water that passes through the tubes of the U-bundle.

The air passes through the shell where, due to pressure drop requirements, a no-tubes-in-window design with side-to-side flow was selected. Robox was able to serve the customer by meeting the requirements regarding pressure drop and installation dimensions.

This is a Shell & Tube heat exchanger. A one-pass shell with U-bundle and removable bonnet header. TEMA type BEU 168 / 900 executed in stainless steel with CuNi 90/10 tubes and muntz metal tube sheet. Designed and built according to PED cat.II/Mod A1 + ASME VIII div.1